So that you can finest fulfill client's demands, all of our operations are strictly performed in line with our motto "High Excellent, Competitive Price, Fast Service" for Ats 10kw Diesel Generator , 100kw Diesel Generator , Dewatering Diesel Pump Set , We welcome an prospect to do enterprise along with you and hope to have pleasure in attaching even more aspects of our items.
2019 China New Design Remote Laptop Control Intelligent Load Bank - 300kW Resistive Load Bank Air Cooled Single Phase Generator Testing – Gff Keypower Detail:


KEYPOWER GENERATOR TESTER SPECIFICATIONS

Measurement

Range

Accuracy

Resolution

Overload

Voltage (V)

10.0~500.0V

± (0.4% reading+0.1%range)

0.1V

600V

Current (A)

0.030~5.000A 

± (0.4% reading+0.1%range)

0.001A

6A

Power

According to volt range 

&  current range

Power factor =1.0

<200W 0.1W

 

± (0.4% reading+0.1% range)

≥200W 1W

Power factor =0.5

≥2kW 10W

± (0.8% reading+0.2% range)

 

Power Factor

0.20~1.00

±0.02

0.001

 

Frequency

45~65Hz

±0.2Hz

0.01Hz

 

Running Time

99h59m

±2min/hour

1 minute

 

Energy
 (kWh)

99999kWh

 Power factor= 1.0

0.001kwh

 

± (0.4% reading+0.1% range)

Power factor=0.5

± (0.8% reading+0.2% range)

Harmonic Analysis 

(%)

2-50 times 

and total harmonic

 

 

 

 

 

Models You Can Choose

Model

Testing 

capacity

Type 

of

 load

Duty

Cooling 

system

Phase

Rated 

Testing 

Voltage

Rated

 Frequency

Dimensions   

   (L*W*H)

 (mm)

Weight

 (kg)

KPLB-100

0 - 100 kw

Resistive 

or 

Reactive, 

 PF = 

1.0 or 0.8

Continuous

Industrial 

grade 

axial fan

Available

 at both 

single 

and 

three 

phase

110-480 

VAC

50/60 Hz

960*1060*1400

350

KPLB-200

0 - 200 kw

1560*1310*1650

837

KPLB-300

0 - 300 kw

1690*1440*1750

1083

KPLB-400

0 - 400 kw

1900*1600*1900

1200

KPLB-500

0 - 500 kw

1900*1600*1900

1400

KPLB-600

0 - 600 kw

2100*1730*2000

1550

KPLB-700

0 - 700 kw

2100*1730*2000

1650

KPLB-800

0 - 800 kw

2400*2330*2100

1750

KPLB-1000

0 - 1000 kw

2400*2330*2200

2150

KPLB-2000

0 - 2000 kw

20 ft container

6000

KPLB-5000

0 - 5000 kw

40HC container

16000

KEYPOWER Load Bank Technical Specifications  

1. Resistive type of load, PF = 1.0. Stainless steel sheathed elements manufactured from high grade nickel-chromium alloys resistive wire covered by 3-year warranty.     
2. Rated testing voltage: AC 3P4W, 110-480 VAC 50/60HZ.     
3. Cooling mode: forced air-cooled, fans mounted on the side of the load bank blow horizontally. External utility power or internal tested power supply for fans.     
4. Working mode: load step control
Total testing capacity ranges from 0kw to the max consisting of 10kw, 20kw, 50kw, 100kw load setting switches plus a 0-10kw fine-tuning knob. From 0kw to the max, any load combination is achievable. Load step resolution is 10kw.  
5. Load bank features world-famous components to ensure reliable performance and longer service life including:

65a0abcd-71ea-4a03-a397-96c028a07077.jpg  contactors.
e6aea9f4-d658-4cf2-bf5e-52b7c1b40c31.jpg  switches, knobs and indicators.
9bd3ece4-27f1-4b5f-b857-8bfe773ff629.jpg  circuit breakers.
5453df63-a87a-446c-90c4-51d14d25bf28.jpg  intermediate relays.
70a2a081-2533-4ddb-a9c6-325378cbe478.jpg  terminal blocks.

6. Parameter measuring accuracy grade: 0.5.
7. Load control accuracy: ±3%.
8. Load bank protections: over heating protection, cooling fans failure protection and over load protection with alarm.
9. Control mode: two control modes available: a) Local manual control; b) Optional: Manual control via a remote control panel (max control distance is 20m).
10. Parameter display and measurement: Control panel contains a  b7523933-9e24-434f-94ce-e90c1b386271.gif  Multifunction Electricity Meter displaying voltage, current, load power, reactive power, apparent power, power factor, frequency etc. (Optional: a professional generator tester displays and measures all sorts of steady, dynamic parameters as well as harmonic wave, can be connected to a PC for data recording and test report printing).

11. Operating environment: Altitude: ≤1000m above sea level. Ambient temp: -10℃~+40℃ Relative humidity: ≤80% ventilated environment without explosive or corrosive dust. Not allowed to use in rainy outdoor environment.


Product detail pictures:

2019 China New Design Remote Laptop Control Intelligent Load Bank - 300kW Resistive Load Bank Air Cooled Single Phase Generator Testing – Gff Keypower detail pictures

2019 China New Design Remote Laptop Control Intelligent Load Bank - 300kW Resistive Load Bank Air Cooled Single Phase Generator Testing – Gff Keypower detail pictures


Related Product Guide:

We have many excellent staff members good at marketing, QC, and dealing with kinds of troublesome problem in the production process for 2019 China New Design Remote Laptop Control Intelligent Load Bank - 300kW Resistive Load Bank Air Cooled Single Phase Generator Testing – Gff Keypower , The product will supply to all over the world, such as: Jordan, Portugal, European, Customer's satisfaction is always our quest, creating value for customers is always our duty, a long term mutual-beneficial business relationship is what we are doing for. We are an absolutely reliable partner for you in China. Of course, other services, like consulting, can be offered too.
  • We have been engaged in this industry for many years, we appreciate the work attitude and production capacity of the company, this is a reputable and professional manufacturer.
    5 Stars By Melissa from British - 2017.10.13 10:47
    We have been appreciated the Chinese manufacturing, this time also did not let us disappoint,good job!
    5 Stars By Nicole from Croatia - 2018.10.01 14:14
    Write your message here and send it to us